KV-8000/7000/5000/3000 CPUAccessory port/KV-LE20V equivalent

<< Click to Display Table of Contents >>

Manuals > Device Connection Guide > Keyence > Connection Procedure (Ethernet) >

KV-8000/7000/5000/3000 CPUAccessory port/KV-LE20V equivalent

About the connection example

Please see below for an example of connection settings for this driver.

 

Applicable models etc.

explanation

Connection example [KV-5000]

This is an example of connection settings with the Keyence KV-5000 series.

 

 

*For connection settings with other compatible models, please refer to the above.

 

 

Device List

The compatible devices are as follows (see here for how to view the device list).

 

device

keyword

Start address

explanation

unit

reading

Writing

Input/Output/Auxiliary Relays

R

000000

Decimal number 4 digits + 2 digits (00 to 15)

bit

○

○

Control Relay

CR

0000

Decimal number 2 digits + 2 digits (00 to 15)

bit

○

○

Link Relay

B

0000

Hexadecimal

bit

○

○

Work Relay

VB

0000

Hexadecimal

bit

○

○

Internal Auxiliary Relay

MR

000000

Decimal number 4 digits + 2 digits (00 to 15)

bit

○

○

Latching Relay

LR

00000

Decimal number 3 digits + 2 digits (00 to 15)

bit

○

○

Timer Contact

T

000

Decimal

bit

○

○

Counter Contact

C

000

Decimal

bit

○

○

High-speed counter contact

CTH

0

Decimal

bit

○

×

High-speed counter comparator contact

CTC

0

Decimal

bit

○

×

Timer setting value

TS

000

Decimal

word

○

●

Counter setting value

CS

000

Decimal

word

○

●

High-speed counter setting value

CTHS

0

Decimal

word

○

×

High-speed counter comparator setting value

CTCS

0

Decimal

word

○

●

Timer current value

TN

000

Decimal

word

○

●

Counter current value

CN

000

Decimal

word

○

●

High-speed counter current value

CTHN

0

Decimal

word

○

●

High-speed counter comparator current value

CTCN

0

Decimal

word

○

×

Temporary Data Memory

TM

000

Decimal

word

○

●

Control Memory

CM

00000

Decimal

word

○

●

Data Memory

DM

00000

Decimal

word

○

●

Expanded Data Memory

EM

00000

Decimal

word

○

●

Expanded Data Memory

FM

00000

Decimal

word

○

●

File Register

ZF

000000

Decimal

word

○

●

Link Register

W

0000

Hexadecimal

word

○

●

Working Memory

VM

00000

Decimal

word

○

●

Index Register

Z

00000

Decimal

word

○

●