Device List

<< Click to Display Table of Contents >>

Manuals > Device Connection Guide > Mitsubishi Electric > Private Protocol > Common Explanation >

Device List

Device List

The supported devices are as follows:

 

Mitsubishi Electric MELSEC-iQ-R series

device

keyword

Start address

explanation

unit

reading

Writing

Input Relay

X

000000

Hexadecimal

bit

○

○

Output Relay

Y

000000

Hexadecimal

bit

○

○

Internal Relay

M

000000

Decimal

bit

○

○

Latching Relay

L

000000

Decimal

bit

○

○

Annunciator

F

000000

Decimal

bit

○

○

Edge Relay

V

000000

Decimal

bit

○

○

Step Relay

S

000000

Decimal

bit

○

○

Link Relay

B

000000

Hexadecimal

bit

○

○

Special Link Relay

SB

000000

Hexadecimal

bit

○

○

Special Relay

SM

000000

Decimal

bit

○

○

Argument Input

FX

000000

Decimal

bit

○

○

Argument Output

FY

000000

Decimal

bit

○

○

Timer Contact

TS

000000

Decimal

bit

○

○

Timer coil

TC

000000

Decimal

bit

○

○

Integration Timer Contact

STS

000000

Decimal

bit

○

○

Accumulator timer coil

STC

000000

Decimal

bit

○

○

Counter Contact

CS

000000

Decimal

bit

○

○

Counter coil

CC

000000

Decimal

bit

○

○

Timer current value

TN

000000

Decimal

word

○

●

Current value of the integration timer

STN

000000

Decimal

word

○

●

Counter current value

CN

000000

Decimal

word

○

●

Data Register

D

000000

Decimal

word

○

●

Index Register

Z

000000

Decimal

word

○

●

Link Register

W

000000

Hexadecimal

word

○

●

Special Link Register

SW

000000

Hexadecimal

word

○

●

Special Registers

SD

000000

Decimal

word

○

●

Buffer Memory

G

000000

Decimal

word

○

●

File register (current block)

R

000000

Decimal

word

○

●

File register (sequential number)

ZR

000000

Hexadecimal

word

○

●

File register (sequential number)

ZZR

0000000

Decimal

word

○

●

 

Mitsubishi Electric MELSEC-Q/L series

device

keyword

Start address

explanation

unit

reading

Writing

Input Relay

X

000000

Hexadecimal

bit

○

○

Output Relay

Y

000000

Hexadecimal

bit

○

○

Internal Relay

M

000000

Decimal

bit

○

○

Latching Relay

L

000000

Decimal

bit

○

○

Annunciator

F

000000

Decimal

bit

○

○

Edge Relay

V

000000

Decimal

bit

○

○

Step Relay

S

000000

Decimal

bit

○

○

Link Relay

B

000000

Hexadecimal

bit

○

○

Special Link Relay

SB

000000

Hexadecimal

bit

○

○

Special Relay

SM

000000

Decimal

bit

○

○

Argument Input

FX

000000

Decimal

bit

○

○

Argument Output

FY

000000

Decimal

bit

○

○

Direct Input

DX

000000

Hexadecimal

bit

○

○

Direct Output

DY

000000

Hexadecimal

bit

○

○

Timer Contact

TS

000000

Decimal

bit

○

○

Timer coil

TC

000000

Decimal

bit

○

○

Integration Timer Contact

SS

000000

Decimal

bit

○

○

Accumulator timer coil

SC

000000

Decimal

bit

○

○

Counter Contact

CS

000000

Decimal

bit

○

○

Counter coil

CC

000000

Decimal

bit

○

○

Timer current value

TN

000000

Decimal

word

○

●

Current value of the integration timer

SN

000000

Decimal

word

○

●

Counter current value

CN

000000

Decimal

word

○

●

Data Register

D

000000

Decimal

word

○

●

Index Register

Z

000000

Decimal

word

○

●

Link Register

W

000000

Hexadecimal

word

○

●

Special Link Register

SW

000000

Hexadecimal

word

○

●

Special Registers

SD

000000

Decimal

word

○

●

Argument Register

FD

000000

Decimal

word

○

●

Buffer Memory

G

000000

Decimal

word

○

●

File register (current block)

R

000000

Decimal

word

○

●

File register (sequential number)

ZR

000000

Hexadecimal

word

○

●

File register (sequential number)

ZZR

0000000

Decimal

word

○

●

 

Mitsubishi Electric MELSEC-QnA series

device

keyword

Start address

explanation

unit

reading

Writing

Input Relay

X

000000

Hexadecimal

bit

○

○

Output Relay

Y

000000

Hexadecimal

bit

○

○

Internal Relay

M

000000

Decimal

bit

○

○

Latching Relay

L

000000

Decimal

bit

○

○

Annunciator

F

000000

Decimal

bit

○

○

Edge Relay

V

000000

Decimal

bit

○

○

Step Relay

S

000000

Decimal

bit

○

○

Link Relay

B

000000

Hexadecimal

bit

○

○

Special Link Relay

SB

000000

Hexadecimal

bit

○

○

Special Relay

SM

000000

Decimal

bit

○

○

Argument Input

FX

000000

Decimal

bit

○

○

Argument Output

FY

000000

Decimal

bit

○

○

Direct Input

DX

000000

Hexadecimal

bit

○

○

Direct Output

DY

000000

Hexadecimal

bit

○

○

Timer Contact

TS

000000

Decimal

bit

○

○

Timer coil

TC

000000

Decimal

bit

○

○

Integration Timer Contact

SS

000000

Decimal

bit

○

○

Accumulator timer coil

SC

000000

Decimal

bit

○

○

Counter Contact

CS

000000

Decimal

bit

○

○

Counter coil

CC

000000

Decimal

bit

○

○

Timer current value

TN

000000

Decimal

word

○

●

Current value of the integration timer

SN

000000

Decimal

word

○

●

Counter current value

CN

000000

Decimal

word

○

●

Data Register

D

000000

Decimal

word

○

●

Index Register

Z

000000

Decimal

word

○

●

Link Register

W

000000

Hexadecimal

word

○

●

Special Link Register

SW

000000

Hexadecimal

word

○

●

Special Registers

SD

000000

Decimal

word

○

●

Argument Register

FD

000000

Decimal

word

○

●

Buffer Memory

G

000000

Decimal

word

○

●

File register (current block)

R

000000

Decimal

word

○

●

File register (sequential number)

ZR

000000

Hexadecimal

word

○

●

File register (sequential number)

ZZR

0000000

Decimal

word

○

●

 

Mitsubishi Electric MELSEC-A series

device

keyword

Start address

explanation

unit

reading

Writing

Input Relay

X

000000

Hexadecimal

bit

○

○

Output Relay

Y

000000

Hexadecimal

bit

○

○

Internal Relay

M

000000

Decimal

bit

○

○

Latching Relay

L

000000

Decimal

bit

○

○

Annunciator

F

000000

Decimal

bit

○

○

Step Relay

S

000000

Decimal

bit

○

○

Link Relay

B

000000

Hexadecimal

bit

○

○

Timer Contact

TS

000000

Decimal

bit

○

○

Timer coil

TC

000000

Decimal

bit

○

○

Counter Contact

CS

000000

Decimal

bit

○

○

Counter coil

CC

000000

Decimal

bit

○

○

Timer current value

TN

000000

Decimal

word

○

●

Counter current value

CN

000000

Decimal

word

○

●

Data Register

D

000000

Decimal

word

○

●

Index Register

Z

000000

Decimal

word

○

●

Index Register

V

000000

Decimal

word

○

●

Link Register

W

000000

Hexadecimal

word

○

●

Accumulation Register

A

000000

Decimal

word

○

●

File Register

R

000000

Decimal

word

○

●

Extended File Register (Block)

R

0000000

Decimal number 3 digits (block number) + 4 digits (0 to 8191)

word

○

●

 

Mitsubishi Electric MELSEC-FX series

device

keyword

Start address

explanation

unit

reading

Writing

Input Relay

X

000000

Octal

bit

○

○

Output Relay

Y

000000

Octal

bit

○

○

Internal Relay

M

000000

Decimal

bit

○

○

Step Relay

S

000000

Decimal

bit

○

○

Timer Contact

TS

000000

Decimal

bit

○

○

Timer coil

TC

000000

Decimal

bit

○

○

Counter Contact

CS

000000

Decimal

bit

○

○

Counter coil

CC

000000

Decimal

bit

○

○

Timer current value

TN

000000

Decimal

word

○

●

Counter current value

CN

000000

Decimal

word

○

●

Data Register

D

000000

Decimal

word

○

●

Index Register

Z

000000

Decimal

word

○

●

Index Register

V

000000

Decimal

word

○

●

 

 

hint

When using buffer memory, specify the address as follows:

 

Mitsubishi Electric side notation:

UxxGyyyyy

Tag Editor side notation:

UGxxyyyyy

 

Example: For "U02G883", enter UG0200883