<< Click to Display Table of Contents >> Manual > Device Connection Guide > Hitachi > Connection Procedure (Ethernet) > HIDIC-S10/2α/mini LWE550/LQE020 equivalent |
About the connection example
Please see below for an example of connection settings for this driver.
Applicable models etc. |
explanation |
This is an example of Ethernet connection settings for the HIDIC-S10mini series.
|
Device List
The compatible devices are as follows (see here for how to view the device list).
device |
keyword |
Start address |
explanation |
unit |
reading |
Writing |
Address specification (16-bit units) |
AW |
060000 |
Hexadecimal |
word |
○ |
● |
Address specification (32-bit units) |
AD |
060000 |
Hexadecimal |
Double Word |
○ |
● |
External Input |
X |
000 |
Hexadecimal |
bit |
○ |
○ |
Transfer Register |
J |
000 |
Hexadecimal |
bit |
○ |
○ |
External Output |
Y |
000 |
Hexadecimal |
bit |
○ |
○ |
Receive Register |
Q |
000 |
Hexadecimal |
bit |
○ |
○ |
Global Link Register |
G |
000 |
Hexadecimal |
bit |
○ |
○ |
Internal Registers |
R |
000 |
Hexadecimal |
bit |
○ |
○ |
Extended Internal Registers |
M |
000 |
Hexadecimal |
bit |
○ |
○ |
Keep Relay |
K |
000 |
Hexadecimal |
bit |
○ |
○ |
On-delay timer (contact) |
TK |
000 |
Hexadecimal |
bit |
○ |
○ |
On-delay timer (coil) |
T |
000 |
Hexadecimal |
bit |
○ |
○ |
One-shot timer (contact) |
UK |
000 |
Hexadecimal |
bit |
○ |
○ |
One-shot timer (coil) |
U |
000 |
Hexadecimal |
bit |
○ |
○ |
Counter (up coil) |
CU |
00 |
Hexadecimal |
bit |
○ |
○ |
Counter (down coil) |
CD |
00 |
Hexadecimal |
bit |
○ |
○ |
Counter (contact) |
C |
000 |
Hexadecimal |
bit |
○ |
○ |
Counter (reset coil) |
CR |
00 |
Hexadecimal |
bit |
○ |
○ |
Nesting coil (contact) |
N |
000 |
Hexadecimal |
bit |
○ |
○ |
Process Coil |
P |
000 |
Hexadecimal |
bit |
○ |
○ |
Edge Contacts |
V |
000 |
Hexadecimal |
bit |
○ |
○ |
Event Register |
E |
000 |
Hexadecimal |
bit |
○ |
○ |
Z Register |
Z |
000 |
Hexadecimal |
bit |
○ |
○ |
System Registers |
S |
000 |
Hexadecimal |
bit |
○ |
○ |
External Input |
XW |
000 |
Hexadecimal |
word |
○ |
● |
Transfer Register |
JW |
000 |
Hexadecimal |
word |
○ |
● |
External Output |
YW |
000 |
Hexadecimal |
word |
○ |
● |
Receive Register |
QW |
000 |
Hexadecimal |
word |
○ |
● |
Global Link Register |
GW |
000 |
Hexadecimal |
word |
○ |
● |
Internal Registers |
RW |
000 |
Hexadecimal |
word |
○ |
● |
Extended Internal Registers |
MW |
000 |
Hexadecimal |
word |
○ |
● |
Keep Relay |
KW |
000 |
Hexadecimal |
word |
○ |
● |
On-delay timer |
TW |
000 |
Hexadecimal |
word |
○ |
● |
One Shot Timer |
UW |
000 |
Hexadecimal |
word |
○ |
● |
Up/down counter |
CW |
000 |
Hexadecimal |
word |
○ |
● |
Nesting coil |
NW |
000 |
Hexadecimal |
word |
○ |
● |
Process Coil |
PW |
000 |
Hexadecimal |
word |
○ |
● |
Edge Contacts |
VW |
000 |
Hexadecimal |
word |
○ |
● |
Event Register |
EW |
000 |
Hexadecimal |
word |
○ |
● |
Z Coil |
ZW |
000 |
Hexadecimal |
word |
○ |
● |
System Registers |
SW |
000 |
Hexadecimal |
word |
○ |
● |
Work Register |
FW |
000 |
Hexadecimal |
word |
○ |
● |
Long word register (32 bits) |
BD |
000 |
Hexadecimal |
Double Word |
○ |
● |
Extended external input |
IW |
000 |
Hexadecimal |
word |
○ |
● |
Extended external output |
OW |
000 |
Hexadecimal |
word |
○ |
● |
Data Register |
DW |
000 |
Hexadecimal |
word |
○ |
● |
On-delay timer (setting value) |
TS |
000 |
Hexadecimal |
word |
○ |
● |
One-shot timer (setting value) |
US |
000 |
Hexadecimal |
word |
○ |
● |
Counter (setting value) |
CS |
000 |
Hexadecimal |
word |
○ |
● |
On-delay timer (count value) |
TC |
000 |
Hexadecimal |
word |
○ |
● |
One-shot timer (count value) |
UC |
000 |
Hexadecimal |
word |
○ |
● |
Counter (count value) |
CC |
000 |
Hexadecimal |
word |
○ |
● |
External input (32bit) |
XL |
000 |
Hexadecimal |
Double Word |
○ |
● |
External output (32bit) |
YL |
000 |
Hexadecimal |
Double Word |
○ |
● |
Internal register (32bit) |
RL |
000 |
Hexadecimal |
Double Word |
○ |
● |
Extended internal register (32bit) |
ML |
000 |
Hexadecimal |
Double Word |
○ |
● |
Data register (32bit) |
DL |
000 |
Hexadecimal |
Double Word |
○ |
● |
Work register (32bit) |
FL |
000 |
Hexadecimal |
Double Word |
○ |
● |
Extended external input (32bit) |
IL |
000 |
Hexadecimal |
Double Word |
○ |
● |
Extended external output (32bit) |
OL |
000 |
Hexadecimal |
Double Word |
○ |
● |
Access to addresses earlier than 060000 is not permitted when specifying absolute addresses. We do not guarantee the operation of the PLC if such addresses are accessed. |
Use "AW" when accessing in word units with absolute addressing. Please specify an even address (multiple of 2). example) Address AW061000 → DW000 Address AW061002 → DW001 Address AW061004 → DW002
・Use "AD" when accessing in double-word units with absolute addressing. Please specify the address in multiples of 4. example) Address AD061000 → DW000 to DW001 are interpreted as long words Address AD061004 → DW002-DW003 are interpreted as long words Address AD061008 → DW004 to DW005 are interpreted as long words
- Long word devices (such as "XL", "YL", and "RL") are not defined in the PLC itself, but are virtually defined for the purpose of handling devices in long word units. These are equivalent to "BW", "XW", and "YW" respectively, but handle values in 32-bit increments. Addresses are specified as even numbers (multiples of 2). |