<< Click to Display Table of Contents >> Manual > Device Connection Guide > Keyence > Connection Procedure (RS-232C) > KZ-700 KV-L20 |
About the connection example
Please see below for an example of connection settings for this driver.
Applicable models etc. |
explanation |
This is an example of connection settings with the Keyence KV-700 series via RS232-C.
|
*For connection settings with other compatible models, please refer to the above.
Device List
The compatible devices are as follows (see here for how to view the device list).
device |
keyword |
Start address |
explanation |
unit |
reading |
Writing |
Input/Output/Auxiliary Relays |
R |
000000 |
4 decimal digits + 2 hexadecimal digits |
bit |
○ |
● |
Control Relay |
CR |
000000 |
4 decimal digits + 2 hexadecimal digits |
bit |
○ |
● |
Temporary Data Memory |
TM |
0000 |
Decimal |
bit |
○ |
● |
Digital trimmer |
TRM |
0000 |
Decimal |
bit |
○ |
● |
Control Memory |
CM |
0000 |
Decimal |
bit |
○ |
● |
Timer/Counter Contact |
TC |
0000 |
Decimal |
bit |
○ |
○ |
High Speed Counter Comparator |
CTC |
0000 |
Decimal |
bit |
○ |
○ |
Timer setting value |
TS |
0000 |
Decimal |
word |
○ |
● |
Counter setting value |
CS |
0000 |
Decimal |
word |
○ |
● |
High-speed counter setting value |
CTCS |
0000 |
Decimal |
word |
○ |
● |
Timer/Counter Current Value |
TCN |
0000 |
Decimal |
word |
○ |
● |
Data Memory |
DM |
0000 |
Decimal |
word |
○ |
● |