Connection example [QnA series]

<< Click to Display Table of Contents >>

Manual > Device Connection Guide > Mitsubishi Electric > Private Protocol > (Deprecated) RS-232C QnA Series >

Connection example [QnA series]

overview

This is an example of connection settings via RS-232C with the QnA series (private protocol).

 

Model used

item

Model etc.

PLC

Q2ACPU

Communication Unit

AJ71QC24

 

Configuration details

item

Setting items

Configuration Example

PC settings

COMPort

Serial port number to connect to

Transmission speed

19200bps

parity

Even

Area code

0

 

 

PLC side settings

Set the switch on the front of the "AJ71QC24". For details about the switch, refer to the manufacturer's manual. After setting as follows, be sure to reset the PLC once.

 

switch

Setting contents

STATION No (x10)

0

STATION No (x0)

0

CH1.Mode

5

CH1.SW01

OFF

CH1.SW02

ON

CH1.SW03

ON

CH1.SW04

ON

CH1.SW05

OFF

CH1.SW06

ON

CH1.SW07

ON

CH1.SW08

ON

CH1.SW09

OFF

CH1.SW10

ON

CH1.SW11

ON

CH1.SW12

OFF

 

*For units with other model numbers, set the "mode setting switch" to "5 (dedicated protocol format 1)", "data bit" to "8 bits", and "stop bit" to "1 bit".