<< Click to Display Table of Contents >> Manual > Device Connection Guide > Mitsubishi Electric > Open Protocol (RS-232C) > AnA/U Extended address equivalent to AJ71UC24 |
About the connection example
Please see below for an example of connection settings for this driver.
Applicable models etc. |
explanation |
This is an example of connection settings via RS-232C with the AnU series.
|
About the A series driver
There are two types of A series drivers:
1.MELSEC-A CPU Normal address
It can be used with all CPUs in the
A series, but the accessible addresses are more limited than those of "MELSEC-AnA/AnU".
2.MELSEC-AnA/AnU Extended Address
The models that can be used are limited to AnA and AnU, but the addresses are extended.
The accessible address range is specified in the Computer Link manual published by the manufacturer. For details, see "Device range when using ACPU common commands" (page 5-36) and "Device range when using AnA/AnUCPU common commands" (page 5-39) in the Computer Link/Multidrop Link Unit User's Manual (manual type name "KEISANKI-U-KP").
Device List
The compatible devices are as follows (see here for how to view the device list).
A series normal address
device |
keyword |
Start address |
explanation |
unit |
reading |
Writing |
Input Relay |
X |
0000 |
Hexadecimal |
bit |
○ |
○ |
Output Relay |
Y |
0000 |
Hexadecimal |
bit |
○ |
○ |
Internal Relay |
M |
0000 |
Decimal |
bit |
○ |
○ |
Special Relay |
M |
9000 |
Decimal |
bit |
○ |
○ |
Latching Relay |
L |
0000 |
Decimal |
bit |
○ |
○ |
Step Relay |
S |
0000 |
Decimal |
bit |
○ |
○ |
Link Relay |
B |
0000 |
Hexadecimal |
bit |
○ |
○ |
Annunciator |
F |
0000 |
Decimal |
bit |
○ |
○ |
Timer Contact |
TS |
000 |
Decimal |
bit |
○ |
○ |
Timer coil |
TC |
000 |
Decimal |
bit |
○ |
○ |
Counter Contact |
CS |
000 |
Decimal |
bit |
○ |
○ |
Counter coil |
CC |
000 |
Decimal |
bit |
○ |
○ |
Timer current value |
TN |
000 |
Decimal |
word |
○ |
● |
Counter current value |
CN |
000 |
Decimal |
word |
○ |
● |
Data Register |
D |
0000 |
Decimal |
word |
○ |
● |
Special Registers |
D |
9000 |
Decimal |
word |
○ |
● |
Link Register |
W |
0000 |
Hexadecimal |
word |
○ |
● |
File Register |
R |
0000 |
Decimal |
word |
○ |
● |
Extended File Register (Block) |
R |
0000000 |
Decimal number 3 digits (block number) + 4 digits (0 to 8191) |
word |
○ |
● |
AnA/U Address extension
device |
keyword |
Start address |
explanation |
unit |
reading |
Writing |
Input Relay |
X |
000000 |
Hexadecimal |
bit |
○ |
○ |
Output Relay |
Y |
000000 |
Hexadecimal |
bit |
○ |
○ |
Internal Relay |
M |
000000 |
Decimal |
bit |
○ |
○ |
Special Relay |
M |
009000 |
Decimal |
bit |
○ |
○ |
Latching Relay |
L |
000000 |
Decimal |
bit |
○ |
○ |
Step Relay |
S |
000000 |
Decimal |
bit |
○ |
○ |
Link Relay |
B |
000000 |
Hexadecimal |
bit |
○ |
○ |
Annunciator |
F |
000000 |
Decimal |
bit |
○ |
○ |
Timer Contact |
TS |
00000 |
Decimal |
bit |
○ |
○ |
Timer coil |
TC |
00000 |
Decimal |
bit |
○ |
○ |
Counter Contact |
CS |
00000 |
Decimal |
bit |
○ |
○ |
Counter coil |
CC |
00000 |
Decimal |
bit |
○ |
○ |
Timer current value |
TN |
00000 |
Decimal |
word |
○ |
● |
Counter current value |
CN |
00000 |
Decimal |
word |
○ |
● |
Data Register |
D |
000000 |
Decimal |
word |
○ |
● |
Special Registers |
D |
009000 |
Decimal |
word |
○ |
● |
Link Register |
W |
000000 |
Hexadecimal |
word |
○ |
● |
File Register |
R |
000000 |
Decimal |
word |
○ |
● |
Extended File Register (Block) |
R |
0000000 |
Decimal number 3 digits (block number) + 4 digits (0 to 8191) |
word |
○ |
● |
Extended file register (sequential number) |
R |
0000000 |
|
word |
○ |
● |