AnA/U Extended address equivalent to AJ71UC24

<< Click to Display Table of Contents >>

Manual > Device Connection Guide > Mitsubishi Electric > Open Protocol (RS-232C) >

AnA/U Extended address equivalent to AJ71UC24

About the connection example

Please see below for an example of connection settings for this driver.

 

Applicable models etc.

explanation

Connection example [AnU series]

This is an example of connection settings via RS-232C with the AnU series.

 

 

 

About the A series driver

There are two types of A series drivers:

 

1.MELSEC-A CPU Normal address
It can be used with all CPUs in the A series, but the accessible addresses are more limited than those of "MELSEC-AnA/AnU".

 

2.MELSEC-AnA/AnU Extended Address
The models that can be used are limited to AnA and AnU, but the addresses are extended.

 

The accessible address range is specified in the Computer Link manual published by the manufacturer. For details, see "Device range when using ACPU common commands" (page 5-36) and "Device range when using AnA/AnUCPU common commands" (page 5-39) in the Computer Link/Multidrop Link Unit User's Manual (manual type name "KEISANKI-U-KP").

 

 

Device List

The compatible devices are as follows (see here for how to view the device list).

 

A series normal address

device

keyword

Start address

explanation

unit

reading

Writing

Input Relay

X

0000

Hexadecimal

bit

Output Relay

Y

0000

Hexadecimal

bit

Internal Relay

M

0000

Decimal

bit

Special Relay

M

9000

Decimal

bit

Latching Relay

L

0000

Decimal

bit

Step Relay

S

0000

Decimal

bit

Link Relay

B

0000

Hexadecimal

bit

Annunciator

F

0000

Decimal

bit

Timer Contact

TS

000

Decimal

bit

Timer coil

TC

000

Decimal

bit

Counter Contact

CS

000

Decimal

bit

Counter coil

CC

000

Decimal

bit

Timer current value

TN

000

Decimal

word

Counter current value

CN

000

Decimal

word

Data Register

D

0000

Decimal

word

Special Registers

D

9000

Decimal

word

Link Register

W

0000

Hexadecimal

word

File Register

R

0000

Decimal

word

Extended File Register (Block)

R

0000000

Decimal number 3 digits (block number) + 4 digits (0 to 8191)

word

 

AnA/U Address extension

device

keyword

Start address

explanation

unit

reading

Writing

Input Relay

X

000000

Hexadecimal

bit

Output Relay

Y

000000

Hexadecimal

bit

Internal Relay

M

000000

Decimal

bit

Special Relay

M

009000

Decimal

bit

Latching Relay

L

000000

Decimal

bit

Step Relay

S

000000

Decimal

bit

Link Relay

B

000000

Hexadecimal

bit

Annunciator

F

000000

Decimal

bit

Timer Contact

TS

00000

Decimal

bit

Timer coil

TC

00000

Decimal

bit

Counter Contact

CS

00000

Decimal

bit

Counter coil

CC

00000

Decimal

bit

Timer current value

TN

00000

Decimal

word

Counter current value

CN

00000

Decimal

word

Data Register

D

000000

Decimal

word

Special Registers

D

009000

Decimal

word

Link Register

W

000000

Hexadecimal

word

File Register

R

000000

Decimal

word

Extended File Register (Block)

R

0000000

Decimal number 3 digits (block number) + 4 digits (0 to 8191)

word

Extended file register (sequential number)

R

0000000

 

word