Event log detection interval by Tag event

<< Click to Display Table of Contents >>

Manual > Server Creation Guide > Action Edition > Action Reference > Logger Action (Logging Only) >

Event log detection interval by Tag event

Tag event detection period

The execution trigger for the logger action of the event-based log is generated by Tag event. Here, the monitoring cycle of the tag value by Tag event depends on the value update cycle setting for the tag folder.

 

The default update interval for tags is 1 second, but if you set the hours, minutes, seconds, and milliseconds to 0 (zero), the values will be monitored at the fastest possible interval. It depends on the number of tags, but the fastest possible update interval is about 15ms to 30ms when connected to a PLC with Ethernet, and about 30ms to 50ms when connected to RS-232C.

 

(Tag folder update cycle setting)