Common to all CPUs
For information on how to set up CPU and various communication units, please refer to the manual for each CPU or unit. The "Timeout" setting in "Advanced Settings" is supported from the following driver package onwards. For earlier driver versions, the driver sets the timeout to 15 seconds.
SW3DNF-CC-Link: 00A or later
Please specify this setting in multiples of 1000 (i.e. in seconds) (the last three digits will be truncated). Also, values between 30000 and 360000 will be valid, values between 0 and 29999 will be treated as 30000, and values over 360001 will be treated as 360000.
Q Series Q Mode
If you select "Multiple CPU - Management CPU" in "Target CPU", "Single CPU" will be selected when you reopen the setting screen. This occurs because the internal settings for both are the same, and does not affect operation.
QnA Series
Access to stations other than the connected station (access to other stations) is not possible.
CC-Link Board
Nothing in particular.