Importing Trends Server Settings

<< Click to Display Table of Contents >>

Manual > Monitoring system construction guide > Construction of main functions > Logging/trend graph > Manual incorporation of trend graph screen library >

Importing Trends Server Settings

overview

This section explains how to manually import the Panel Server side settings from the screen library sample.

 

In addition, for projects generated using the standard framework, summary action settings are usually pre-built in, so there is no need to import each setting manually.

 

The steps introduced here should be performed in the following cases:

 

•For your own projects that do not use standard frameworks.

•If you are using the standard framework, but the summary action settings have been deleted (for example, if you add logging functionality later after implementation).

 

 

hint

The steps introduced on this page assume that the root folder of the Panel Server application settings/system settings is set as follows. Also, when importing actions from a sample, the settings for each action are set with a relative path. This setting allows the project to continue working even if the folder name or folder hierarchy of the project folder changes.

If you do not specify a root folder, such as when importing a screen library into your own project, make adjustments according to the project environment, such as making sure the relative path reference locations match, or defining the reference destination of each file with an absolute path. For details, see "System Settings" in the Panel Server application settings.

 

(system settings root folder)

parts_howto_0191

 

 

 

Manually importing server settings

Below are the steps to manually import the Panel Server side settings from the trend graph screen library sample.

 

■ Work procedure

 

1.Open Panel Server

 

With the project you are currently working on open, right-click "server.txt" in the Panel Editor tree to display the menu, and select "Open Server" from the menu.

 

This will start Panel Server with the target server configuration file open.

 

 

2.Open the Screen Library sample

 

Select the Library tab of the Panel Editor you are currently working in and select the "Trend Graph" thumbnail from the Screen Library.

 

p_logger_0081

 

When you select a thumbnail, a description of the screen library's functions will be displayed, so click the "Sample" button at the bottom.

 

 

 

 

 

This will start a new Panel Editor separate from the Panel Editor you are currently using, with the sample project open.

 

 

3.Open the sample project's server configuration file in edit mode

 

Right-click on "server.txt" in the left tree of the newly opened Panel Editor to display the menu and select "Open Server (Edit Mode)."

 

p_logger_0082

 

This will start another Panel Server in edit mode with the sample server configuration file open.

 

p_alarm_0070

 

In edit mode on Panel Server, the various icons for online operations are in a dim state as shown on the left, and online operation cannot be performed.

 

By opening a sample server configuration file in this mode, you can copy settings such as actions and events between Panel Server.

 

 

 

 

 

 

 

 

hint

Panel Server cannot be started multiple times at the same time in normal mode. You can start another one only if you open it in edit mode.

 

 

4.Import the "Summary" action from the sample

 

First, arrange the windows so that both the Panel Server you are currently working on and the Panel Server with the sample open in edit mode are visible, as shown in the image below.

 

 

p_logger_0085

 

In this state, drag and drop the "Summary" action registered under the Action of the sample Panel Server onto the "Action" of the Panel Server you are currently working on.

 

 

p_logger_0083

 

The Summary will then be copied under Action on the Panel Server side you are currently working on.

 

p_logger_0087

 

 

5.Capture "Summary" related events from the sample

 

Next, we'll import the events we need.

 

First, click and open "Event" on the sample Panel Server side. Under the "Summary" folder registered under the event, you will see a Scheduled event called "LOG". This Scheduled event is an event that periodically calls the Summary action.

 

p_logger_0088

 

Similar to the procedure for importing the action, drag and drop the "Summary" folder registered in Event of the sample Panel Server onto the "Event" of the Panel Server you are currently working on.

 

 

p_logger_0089

 

The "Summary" folder was then copied to the events of the Panel Server you were currently working on, along with the "LOG" event.

 

p_logger_0091

 

 

6.Import the necessary folders from the sample

 

Next, copy the necessary files and folders from the sample project. In the Panel Editor where the sample project is open, right-click "server.txt" in the tree on the left to display the menu, and select "Open Explorer".

 

p_logger_0092

 

This will launch Explorer with the location where the sample server configuration file is stored.

 

p_logger_0093

 

Here, the folder that needs to be imported is the "summary" folder under the server folder of the sample project.

 

From Explorer,Copy the entire "summary" folder into the server folder in the project folder you are currently working on.

 

 

 

 

7.Set up the public folder for Panel-Interface

 

Next, go to the Panel Server's Panel-Interface settings and set up the public folder required for this screen library.If the necessary public folders are already registered, there is no need to configure this.

 

In the left tree of the Panel Server you are currently working on, right-click on Interface "Panel" and display its properties.

 

p_logger_0371

 

Select the "Public Folders" tab in the Properties dialog and click the "Add" button.

 

p_logger_0372

 

On the public folder settings screen, enter the following information and click the OK button.

 

p_logger_0373

 

•Enable public folder: Check

•Public Folder Name: server_data_cnf

•Public folder: server_data\config

•Allow files to be read only: Uncheck

 

Verify that the contents you added are reflected in the public folder list, then click the OK button in the Properties dialog to save the settings.

 

p_logger_0374

 

 

This completes the import of the necessary settings.

 

You need to configure logging for the various master files of the summary actions imported from the sample.

For information on how to edit the tag field master of a summary action, see "Editing Tag Field Master".