Operational monitoring design

<< Click to Display Table of Contents >>

Manual > Monitoring system construction guide > Establishing major functions > Operation monitoring > Practical operation monitoring > Introduction level 1) Simple operation monitoring >

Operational monitoring design

Equipment requirements for this example

In this configuration example, we assume that there is monitored equipment with the following requirements:

 

•In a factory for producing certain parts, five pieces of machinery and equipment are installed for production.

•Each of the five pieces of mechanical equipment is equipped with a contact point for outputting a signal indicating "operating" or "stopped" to the outside.

 

We will input the "operating" and "stopped" signals from the above machinery and equipment to perform simple operation monitoring.

 

•The operating/stopped state is indicated by changes in the left indicator light and the background color of the display frame.

•No message display is used.

•Production results will not be imported.

•Displays data on "operating time," "operating count," "stopped time," "count of stoppages," "continuous operating time," and "operating rate."

 

 

■ Signals to be captured (examples)

 

The following contact signals are to be received via downstream devices such as remote I/O.

In this example, all contact signals are taken in through a single downstream device, "Device 1."

 

Equipment Title

Equipment Subtitle

Acquisition Signal

How to import

remarks

Machinery Equipment 01

Part P01

While driving

Device 1/DI/ Contact capture

ON: Driving



Suspended

Device 1/DI/ Contact capture

ON: Currently stopped

Machinery Equipment 02

Part P02

While driving

Device 1/DI/ Contact capture

ON: Driving



Suspended

Device 1/DI/ Contact capture

ON: Currently stopped

Machinery Equipment 03

Part P03

While driving

Device 1/DI/ Contact capture

ON: Driving



Suspended

Device 1/DI/ Contact capture

ON: Currently stopped

Machinery Equipment 04

Part P04

While driving

Device 1/DI/ Contact capture

ON: Driving



Suspended

Device 1/DI/ Contact capture

ON: Currently stopped

Machinery and Equipment 05

Part P05

While driving

Device 1/DI/ Contact capture

ON: Driving



Suspended

Device 1/DI/ Contact capture

ON: Currently stopped

 

 

hint

The "Device 1" part above should refer to downstream devices such as PLC and remote I/O that are connected from Panel Server. There are various methods for capturing signals from equipment. "Tag registration for collecting operation status" introduces several specific examples of signal capture methods. Please use this as a reference when building an actual system.

 

 

Unit/tag design

Based on the above equipment requirements, a list of signals that the system needs to capture is designed as a "tag list."

 

■ Tag list (example)

 

In this example, the unit name for connecting to the downstream device "Device 1" is defined as "U01", and a tag for contact signal import is defined under U01.

 

No.

Signal Name

unit

folder

tag

address

type

remarks

1

Machinery 01 in operation

U01

F01

X0000

X0000

bit

ON: Driving

2

  〃〃   Stopped

U01

F01

X0001

X0001

bit

ON: Currently stopped

3

Machinery 02 in operation

U01

F01

X0002

X0002

bit

ON: Driving

4

  〃〃   Stopped

U01

F01

X0003

X0003

bit

ON: Currently stopped

5

Machinery 03 in operation

U01

F01

X0004

X0004

bit

ON: Driving

6

  〃〃   Stopped

U01

F01

X0005

X0005

bit

ON: Currently stopped

7

Machinery 04 in operation

U01

F01

X0006

X0006

bit

ON: Driving

8

  〃〃   Stopped

U01

F01

X0007

X0007

bit

ON: Currently stopped

9

Machinery 05 in operation

U01

F01

X0008

X0008

bit

ON: Driving

10

  〃〃   Stopped

U01

F01

X0009

X0009

bit

ON: Currently stopped

 

 

hint

The above design documents are called "tag lists" or "device lists." We recommend that you prepare the above information when building any monitoring system using SCADA, not just an operation monitoring system.