<< Click to Display Table of Contents >> Manual > Monitoring system construction guide > Construction of major functions > Energy management (EMS) > Practical energy management > Example of group settings for energy management |
Example of group settings
There are two grouping concepts on the energy management screen: "point groups" and "graph groups."
Here we will introduce some specific examples of the point groups and graph groups that are actually set up in this sample.
|
If you want to know the basic concept of energy management grouping, please refer to "Point Groups and Graph Groups". |
■ Equipment requirements for this setting example
In this configuration example, we assume that there is monitored equipment with the following requirements:
•The business entity can be broadly divided into three parts: Head Office, Business Office A, and Business Office B.
•The head office is divided into two floors, "1F" (department 1) and "2F" (department 2). Business office A and business office B are each considered as one department.
•There are three air conditioners in the head office, which are shared throughout the entire office.
•The common areas of the head office include a shop, outdoor lighting, and common areas (such as the entrance), which are used by the entire head office.
•The head office is equipped with solar power generation facilities, and the electricity generated by these facilities is shared and used throughout the entire head office.
•The floor area of the first and second floors of the head office is roughly 7:3. Therefore, the floor area ratio for air conditioners, common areas, and solar power generation will be 7:3 for the first and second floors.
•Gas is only used by the head office. There is one parent gas meter for the entire building and one child meter that shows the gas usage for the 1st floor. The gas usage for the 2nd floor can be calculated by subtracting the total from the 1st floor.
•Data on outside temperature, outside humidity, and rainfall is collected as measurement points.
In addition, the following fields are registered in the summary action as the above metering points and measurement points, and logging, daily report aggregation, monthly report aggregation, and annual report aggregation are performed.
Field Name |
name |
unit |
remarks |
T000 |
Head office air conditioner 1 power consumption |
kWh |
Air conditioners shared across the head office. The usage ratio between 1st and 2nd floors is 7:3. |
T001 |
Head office air conditioner 2 power consumption |
kWh |
Ibid. |
T002 |
Head office air conditioner 3 power consumption |
kWh |
Ibid. |
T003 |
Headquarters 1F lighting power consumption |
kWh |
|
T004 |
Headquarters 2nd floor lighting power consumption |
kWh |
|
T005 |
Headquarters 1F outlet power consumption |
kWh |
|
T006 |
Headquarters 2F outlet power consumption |
kWh |
|
T007 |
Head office exterior lighting power consumption |
kWh |
Head office common area. The usage ratio of 1st and 2nd floors is 7:3. |
T008 |
Electricity consumption at head office store |
kWh |
Ibid. |
T009 |
Electricity consumption for head office common area |
kWh |
Ibid. |
T010 |
Head office gas usage (main meter) |
m3 |
Gas usage throughout the head office. |
T011 |
Head office 1F gas usage (sub meter) |
m3 |
Gas usage for the 1st floor of the head office only. Gas usage for the 2nd floor is calculated by total - 1st floor. |
T012 |
Air conditioner power consumption at business site A |
kWh |
|
T013 |
Power consumption at outlet of business site A |
kWh |
|
T014 |
Lighting power consumption at business site A |
kWh |
|
T015 |
Business site B air conditioner power consumption |
kWh |
|
T016 |
Business location B outlet power consumption |
kWh |
|
T017 |
Lighting power consumption at business site B |
kWh |
|
T018 |
Outside temperature |
℃ |
|
T019 |
Outside humidity |
%RH |
|
T020 |
Rainfall |
mm |
|
T021 |
Solar power generation at head office |
kWh |
Power generation equipment shared with the head office. The usage ratio of 1F and 2F is 7:3. |
■ Group setting example
Below is a concrete example of group configuration based on the above assumptions.
Graph Group |
Conversion Graph |
Proration |
Point Groups |
Consumption/Power Generation |
Weighing Point |
remarks |
Head Office 1F Power Breakdown |
[ ] |
70 |
001 Head Office Air Conditioning Power |
Consumption |
T000 Head Office Air Conditioner 1 Power Consumption |
Air conditioning power is apportioned 7:3 between the 1st and 2nd floors. |
Consumption |
T001 Headquarters air conditioner 2 power consumption |
|||||
Consumption |
T002 Headquarters air conditioner 3 power consumption |
|||||
100 |
006 Head Office 1F Lighting Power |
Consumption |
T003 Headquarters 1F lighting power consumption |
|||
100 |
007 Head Office 1F Power Outlet |
Consumption |
T005 Head Office 1F Power Consumption |
|||
70 |
004 Head Office Shared Power |
Consumption |
T007 Headquarters exterior lighting power consumption |
Shared electricity will be apportioned between the 1st and 2nd floors in a ratio of 7:3. |
||
Consumption |
T008 Head Office Shop Power Consumption |
|||||
Consumption |
T009 Headquarters common area power consumption |
|||||
70 |
021 Headquarters solar power generation |
Power generation |
T021 Headquarters solar power generation capacity |
70% of the electricity generated is assumed to be 1F. |
||
Head Office 2F Power Breakdown |
[ ] |
30 |
001 Head Office Air Conditioning Power |
Consumption |
T000 Head Office Air Conditioner 1 Power Consumption |
Air conditioning power is apportioned 7:3 between the 1st and 2nd floors. |
Consumption |
T001 Headquarters air conditioner 2 power consumption |
|||||
Consumption |
T002 Headquarters air conditioner 3 power consumption |
|||||
100 |
008 Head Office 2F Lighting Power |
Consumption |
T004 Head Office 2F Lighting Power Consumption |
|||
100 |
009 Head Office 2F Power Outlet |
Consumption |
T006 Head Office 2F Power Consumption |
|||
30 |
004 Head Office Shared Power |
Consumption |
T007 Headquarters exterior lighting power consumption |
Shared electricity will be apportioned between the 1st and 2nd floors in a ratio of 7:3. |
||
Consumption |
T008 Head Office Shop Power Consumption |
|||||
Consumption |
T009 Headquarters common area power consumption |
|||||
30 |
021 Headquarters solar power generation |
Power generation |
T021 Headquarters solar power generation capacity |
2F accounts for 30% of the electricity generated. |
||
Head Office Gas Breakdown |
[ ] |
100 |
010 Head Office 1F Gas |
Consumption |
T011 Head Office 1F Gas Usage (Sub-meter) |
|
100 |
011 Head Office 2F Gas |
Consumption |
T010 - T011 |
Calculated using parent meter - child meter. |
||
main office |
[✔] |
100 |
001 Head Office Air Conditioning Power |
Consumption |
T000 Head Office Air Conditioner 1 Power Consumption |
|
Consumption |
T001 Headquarters air conditioner 2 power consumption |
|||||
Consumption |
T002 Headquarters air conditioner 3 power consumption |
|||||
100 |
002 Head Office Lighting Power |
Consumption |
T003 Headquarters 1F lighting power consumption |
|||
Consumption |
T004 Head Office 2F Lighting Power Consumption |
|||||
100 |
003 Head Office Power Outlet |
Consumption |
T005 Head Office 1F Power Consumption |
|||
Consumption |
T006 Head Office 2F Power Consumption |
|||||
100 |
021 Headquarters solar power generation |
Power generation |
T021 Headquarters solar power generation capacity |
|||
100 |
004 Head Office Shared Power |
Consumption |
T007 Headquarters exterior lighting power consumption |
|||
Consumption |
T008 Head Office Shop Power Consumption |
|||||
Consumption |
T009 Headquarters common area power consumption |
|||||
100 |
005 Head Office Gas |
Consumption |
T010 Head office gas usage (parent meter) |
|||
Business location A |
[✔] |
100 |
012 Office A Air conditioning power |
Consumption |
T012 Office A air conditioner power consumption |
|
100 |
013 Office A Power Outlet |
Consumption |
T013 Power consumption at outlets in business location A |
|||
100 |
014 Office A Lighting power |
Consumption |
T014 Office A lighting power consumption |
|||
Business location B |
[✔] |
100 |
015 Office B Air conditioning power |
Consumption |
T015 Office B air conditioner power consumption |
|
100 |
016 Office B Power Outlet |
Consumption |
T016 Business location B outlet power consumption |
|||
100 |
017 Office B Lighting power |
Consumption |
T017 Office B lighting power consumption |
|||
Power Rank by Department |
[ ] |
100 |
018 Head Office 1F Power |
Consumption |
T000 Headquarters air conditioner 1 power consumption* 0.7 |
70% of the air conditioning power is assumed for the first floor. |
Consumption |
T001 Headquarters air conditioner 2 power consumption* 0.7 |
|||||
Consumption |
T002 Headquarters air conditioner 3 power consumption* 0.7 |
|||||
Consumption |
T003 Headquarters 1F lighting power consumption |
|||||
Consumption |
T005 Head Office 1F Power Consumption |
|||||
Consumption |
T007 Head office exterior lighting power consumption* 0.7 |
70% of the electricity for the common areas will be used for the 1st floor. |
||||
Consumption |
T008 Head Office Shop Power Consumption* 0.7 |
|||||
Consumption |
T009 Electricity consumption in the head office common area * 0.7 |
|||||
100 |
019 Head Office 2F Power |
Consumption |
T000 Headquarters air conditioner 1 power consumption* 0.3 |
Assume that 30% of the air conditioning power is for the 2nd floor. |
||
Consumption |
T001 Headquarters air conditioner 2 power consumption* 0.3 |
|||||
Consumption |
T002 Headquarters air conditioner 3 power consumption* 0.3 |
|||||
Consumption |
T004 Head Office 2F Lighting Power Consumption |
|||||
Consumption |
T006 Head Office 2F Power Consumption |
|||||
Consumption |
T007 Head office outdoor lighting power consumption* 0.3 |
30% of the shared power will be for 2F. |
||||
Consumption |
T008 Head Office Shop Power Consumption* 0.3 |
|||||
Consumption |
T009 Electricity consumption in the head office common area * 0.3 |
|||||
100 |
020 Business A Electricity |
Consumption |
T012 Office A air conditioner power consumption |
|||
Consumption |
T013 Power consumption at outlets in business location A |
|||||
Consumption |
T014 Office A lighting power consumption |
|||||
100 |
021 Business B Electricity |
Consumption |
T015 Office B air conditioner power consumption |
|||
Consumption |
T016 Business location B outlet power consumption |
|||||
|
Consumption |
T017 Office B lighting power consumption |
■Explanation
A point group can have multiple metering points registered across multiple point groups. When assigning metering points to a point group, it is possible to write an arithmetic expression, and by writing an expression such as *0.7, the metering value can be apportioned and imported (example: common area electricity), or the calculation results of metering points can be imported (example: gas meter).
In addition, multiple point groups can be registered in a graph group, overlapping across the graph groups. When assigning a point group to a graph group, it is possible to specify an apportionment ratio, and the total value of the point group can be apportioned and imported into the graph group.
Of the graph groups above, "Entire head office", "Power at business site A", and "Power at business site B" are set up with the assumption that they will be displayed on the conversion graph. The graph group settings include a check box for whether or not to display on the conversion graph, and the converted total value for each checked graph group is displayed as a single bar on the conversion graph. In this example, by checking "Entire head office", "Power at business site A", and "Power at business site B", the totals for each of these three graph groups will be displayed as three bar graphs. Note that measurement points can be registered in duplicate in a point group, so make sure to set it so that the values add up when the conversion graph is displayed (so that measurement values are not tallied up in duplicate).
In addition, at the head office, the electricity generated by the solar power generation equipment, which is a form of energy creation, is recorded as "power generation," making it possible to display the amount of power generated on the consumption/power generation display in the usage graph.
Of the graph groups above, "Power Rank by Department" is a group that was registered with the intention of displaying it in a ranking graph. The ranking graph is displayed in order of the number of point groups registered in the graph group. Therefore, in addition to preparing a graph group for ranking display, you should also register point groups in the units for which you want to display rankings.