|
<< Click to Display Table of Contents >> Manual > Library Reference > Screen Library > Screen Library Reference > Trend Graph > Open parameters |
Open parameters in trend graph
|
For information on how to call a screen library using open parameters, see "About open parameters of screen libraries". |
This screen library provides the following open parameters.
name |
Parameters |
explanation |
||||||||
Show/hide setting button |
IsConfig
|
Specifies whether to show or hide the settings button.
|
||||||||
Enable/disable display state retention |
EnabledSaveConfig |
Specifies whether to enable or disable "Keep display state" in the settings menu.
|
||||||||
Real-time updates
|
IsRealTime
|
Specifies whether to display the trend graph in real time.
|
||||||||
Selection method |
Mode |
Specify the parameter selection mode as a string. If omitted, it will operate as "SELECT". For details, see "How to specify Mode parameters" at the bottom of this page.
|
||||||||
Group Name |
GroupName
|
Specify the group name you want to display in the graph as a string. This parameter is used in combination with the Mode parameter above. For details, see "How to specify the Mode parameter" at the bottom of this page. Note that if the DataSource parameter is specified, this parameter will be ignored.
If you want to specify only one group, write it as follows (the group name is an example).
"GroupName:group01"
If you want to specify multiple groups, separate them with commas as follows:
"GroupName:group01,group02,group03"
|
||||||||
Pen name |
PenName
|
Specify the pen name you want to display on the graph as a string. This parameter is used in combination with the Mode parameter above. For details, see "How to specify the Mode parameter" at the bottom of this page. Note that if the DataSource parameter is specified, this parameter will be ignored.
If you want to specify only one pen, write it as follows (note that the pen name is an example).
"PenName:pen01"
If you want to specify multiple pens, separate them with commas as follows:
"PenName:pen01,pen02,pen03"
|
||||||||
Data Source Name |
DataSource |
Specify the data source name (data source path) you want to display on the graph as a string. The pen setting information is searched for based on the specified data source name, and all corresponding pens are displayed on the graph. When using this parameter, the pen information corresponding to the specified data source must be registered as a pen setting. This parameter is used in combination with the Mode parameter. For details, see "How to specify the Mode parameter" at the bottom of this page. Note that if this parameter is specified, GroupName and PenName will be ignored.
If you want to specify only one data source, write it as follows (※The data source name is an example).
"DataSource:T01" ・・・ Example of logger action etc. "DataSource:Summary.RAW::T001" ・・・ Example of summary action
If you want to specify multiple data sources, separate them with commas as follows:
"DataSource:T01,T02,T03" ・・・ Example of logger action etc. "DataSource:Summary.RAW::T001,Summary.RAW::T002,Summary.RAW::T003" ・・・ Example of summary action
|
||||||||
Filter Color |
FilterColor
|
If you specify "FILTER" for the Mode parameter, you can specify the pen display color as a string in RGB format. If a mode other than FILTER is specified, this parameter will be ignored.
If you specify only one as shown below, all pen colors will be displayed in the same color.
"FilterColor:#FF0000"
By specifying multiple colors separated by commas as shown below, you can specify the order in which the colors will be added to AddPen.
"FilterColor:#FF0000,#00FF00"
You can specify a color for each pen name by specifying the combination of "pen name:color format" as shown below.
"FilterColor:Pen 1:#FF0000,Pen 2:#00FF00,Pen 3:#FF0000"
|
||||||||
Start time |
StartDate
|
Specify the start date and time of the graph display period. Specify the date and time in the format specified in the _DeteTimeFormat custom property of the screen library. If this parameter is not specified, the start date and time will be calculated and displayed from the date and time specified in EndDate and the number of seconds specified in TimeSpan. |
||||||||
End Time |
EndDate
|
Specify the end date and time of the graph display period. Specify the date and time in the format specified in the _DeteTimeFormat custom property of the screen library. If this parameter is not specified, the end date and time will be calculated and displayed from the date and time specified in StartDate and the number of seconds specified in TimeSpan. |
||||||||
Graph display span |
TimeSpan
|
Specifies the time span of the graph display in seconds. If this parameter is not specified, the time span setting for the corresponding pen group will be used. |
||||||||
Pen list display |
IsGridDisplay
|
Specifies whether to show or hide the pen list (pen grid) located at the bottom of the screen.
|
||||||||
Header Display |
IsHeader
|
Specifies whether to show or hide the various operation UIs (combo boxes, edit boxes, buttons, etc.) located at the top of the screen.
|
||||||||
Library Unique Name |
LibraryUniqueName
|
When registering multiple identical screen libraries at the same time, specify an identifier in this parameter. The specified identifier must be unique across the entire system. |
How to specify the Mode parameter
Depending on the setting of the Mode parameter, the various behaviors when the GroupName, PenName, and DateSource parameters are specified will be as follows.
Mode parameter setting |
Operation |
|||||||||||||||||
SELECT
|
The screen opens as a normal trend screen, and the groups and pens that meet the conditions specified by the parameters are displayed in selected state.
|
|||||||||||||||||
SEARCH
|
A temporary group named "(INFO)" is created at the top of the group combo box, and pens that meet the conditions specified by the GroupName, PenName, and DataSource parameters are added to this group and displayed. Other groups are displayed as usual.
|
|||||||||||||||||
FILTER
|
A single temporary group named "(INFO)" is created in the group combo box, and pens that meet the conditions specified by the GroupName, PenName, and DataSource parameters are added to that group and displayed. Other groups are not displayed.
|