<< Click to Display Table of Contents >> Manual > Monitoring system construction guide > Construction of main functions > Daily reports > Construction of daily report function > Creating a new standard project |
Creating a new standard project
The following explains how to create a new project that includes the daily report function using the wizard function of the standard framework.
For detailed instructions on creating a standard project using the wizard, please refer to "Creating a Standard Project".
|
The standard project comes with samples, which you can open in Panel Editor. For more information on how to open the samples, see "Frame Library Help/About the Samples". |
■ Work procedure
1.From the start page, select "Create a new project"
From the Panel Editor start page, click "Create New Project."

2.Select the standard framework and open "Create"
Click "Standard Framework" from the list displayed on the start page, and then click the "Create" button displayed at the bottom of the screen.

3.Setting the display style of the project's basic information and display frame
Follow the on-screen instructions to set basic project information (project name, project folder, etc.).
4.In the Select standard features to include in your project section, select the features you want.
From the screen below, you can select the features you want to include in your project.

You can include features in your project by checking the features you want to include in your project.
(enabled state)
|
(Disabled state)
|
In this example, check "Daily Report" and click the Complete button.

When you view the automatically generated project in the workspace tree of Panel Editor, you can see that it contains a "_Summary" folder. Various forms related to the daily report screen are stored in this folder.

Server settings for standard projects
The standard project generated by the above procedure has the following summary action "Summary" defined by default.

And in the "Summary" folder under events, an Scheduled event called "LOG" is registered as an event to call the above.

In this Scheduled event setting, Yearly, Monthly, Daily, Hourly, Minute, and Repeat are checked. This setting causes the event to occur every second with a 1 second period.

The execution action for this event is the "Summary" action. With this setting, Summary will be called every second, resulting in logging at a 1-second interval.

Additionally, the following Scheduled event is registered in the "Summary" folder.
These Scheduled event implement the automatic printing of daily reports and the automatic CSV output function.

What happens |
Scheduled event name |
Default setting date and time |
Automatic daily report printing |
PRINTREPORT_DAY |
Everyday at 00:05 |
Automatic monthly report printing |
PRINTREPORT_MONTH |
00:06 on the first day of every month |
Automatic printing of annual reports |
PRINTREPORT_YEAR |
Every year at 00:07 on January 1st |
Daily report CSV automatic output |
CREATECSV_DAY |
Everyday at 00:10 |
Monthly report CSV automatic output |
CREATECSV_MONTH |
1st of every month at 00:11 |
Annual report CSV automatic output |
CREATECSV_YEAR |
Every year at 00:12 on January 1st |
For details about the parameters for automatic printing and automatic CSV saving registered in the above events, see "Summary Action" in the Action Reference and "Daily Report" in the Library Reference.